Sensor and fan nodes for the signals inverters don't report.

Inverters tell you about strings and AC output. They say nothing about the transformer enclosure getting hot or a cooling fan that is powered but not running. Our sensor nodes cover those points, run their control loop locally, and report to the edge node over MQTT.

Transformer · temperature controlfan nodefan current confirmedfan threshold
MQTT
To the edge node
On the node
Fan control loop
Current draw
Fan running check
In production
On our transformer stations

Keep the transformer station inside its temperature band.

Each node reads the temperature in the transformer station and switches the cooling fans with a hysteresis band: on above the upper threshold, off only once it falls below the lower one, so the fans don't short-cycle. The thresholds are set in the platform, pushed to the node and kept there, so the node applies them itself.

  • Warning and critical alerts. Separate from the fan thresholds, so a normal fan cycle never raises an alert. They resolve themselves when the station cools.
  • Manual, then back to auto. An operator can force the fans on or off from the dashboard and hand control back to the automatic loop with one click.
  • Every command logged. Each relay command is stored with its mode and when it was sent, next to the plant's other commands.
DYNVOLT owner console sensors page: transformer station temperatures, fan relay state and fan current per sensor node
CURRENT SENSOR ON SUPPLYRELAY ON · CURRENT DRAWN

Powered is one state. Running is another.

A fan can have power and still not turn: a seized bearing, a blown capacitor, a broken wire after the relay. So the node does not trust the relay state. A current sensor on each fan's supply confirms the motor is drawing current. When the command says on and the fan draws nothing, the platform raises a fan fault for that station.

When the link drops, the node keeps working.

The fan loop runs on the node, not in the cloud and not on the edge node. If the network to the station goes down, the node keeps reading temperature and switching fans on its last thresholds. When the link returns, its state is back on the dashboard and the alerts catch up.

  • Weather stations. Irradiance and module temperature from on-site cells feed the forecasts, the efficiency views and the reports.
  • Same data store. A transformer temperature and an inverter reading land in the same time series with the same timestamp, so they line up in every chart.

Anything else, built to order.

If a signal you need isn't on a Modbus map anywhere, such as a door contact, a tracker fault line or an extra temperature point, we scope a node for it as a project: what it measures, how it reports, and what it costs, in writing before you commit.

FAQ

Edge hardware: frequently asked

Can't find what you're looking for? Talk to our team →

Do I have to buy DYNVOLT hardware?
No. The platform runs on a Linux edge gateway and reads your existing loggers and inverters. Our sensor and fan nodes are for signals inverters do not report, such as transformer temperature and whether a cooling fan is actually moving air.
How does fan validation work?
Each fan bank's current draw is measured. When the fan is commanded on and the reading says it is not running, the node raises an alarm, so a dead fan is caught before the transformer overheats.
What happens on comms loss?
Thresholds and fan staging run on the node itself over MQTT on the plant network. The node keeps cooling the transformer on its own and the edge buffers the events until the link returns.

Hardware that reports into the same stack.

Every node writes to the same time series as the SCADA. Ask us to show the sensor page on our own transformer stations.

Read the architecture →Request a demo